McFarland Door Manufacturing
Company, Inc.

Address: P.O. Box 848 Lakeview, OR 97630         Phone: 541/947-5136   Fax: 541/947-3094

60-, 90-Minute Fire Doors
Installation Instructions

  1. All McFaraland 60-, 90-minute fire doors have required intumescent seals (if any) built into the door. Therefore no additional seals are required (Exception:) When hung in a pair (positive pressure only) with a (lockset) strike and surface or flush bolts, either to steal flat bar astragal installed on the strike plate.

  2. Pre-drill hinge screw holes for a 2", #12 screw, and install hinges with 2" screws.

  3. Pre-drill all lock mounting screws as gollows and install locks:
                  Mortise locks           2- 2" x #12 sheet metal screws
                  Cylindrical locks       2- 1.5" x #8 sheet metal screws


  4. When installed in a Pair (positive pressure only), a metal dust box for 4 7/8" strike will be supplied and must be installed. Pre-drill and install 1 each #8 x 1.5" sheet metal screw through back of box.

See Fire Doors for more information on fire doors.





Made in USA